VIPERDependencies & Resilience
Know what the service depends on.
See the network, service and power dependencies behind a service, where redundant paths converge, which connections are recorded and which are missing — and what continuity would rely on, stated as a model with its assumptions.
Dependencies · Records Gateway
Dependencies · SVC-01 Records Gateway
- Shared · SW-01 Both hosts of the four services reach the network through one top-of-rack switch.
- Shared · TRUNK-07 Primary (ch04) and secondary (ch03) uplinks ride one trunk; its route is documented, not surveyed.
- Shared · SW-02 Since record rev 15–16 both uplinks terminate on SW-02; its counters are not observed.
- Shared · UPS-01 SRV-01’s two supplies run separately to their breakers and converge on one UPS.
- Missing · into PP-02 The primary segment from TRUNK-07 ch04 to PP-02 is unresolved.
- Missing · patch lead The secondary patch lead at PP-02 P07 has no cable record.
RecordedDocumented onlyUnresolved mappingNo cable recordShared failure domainObserved symptom — not a cause
Synthetic presentation data
Network and service dependencies
Which services ride
which path.
Four services on two hosts reach the network through SW-01 and its uplinks. The view keeps three readings apart: what an independent check observed, which recorded path a service is exposed to, and what a modeled scenario would leave it relying on.
INC-024SVC-01 · Records Gateway
Incident window10:05–10:35 UTC
Service consequence · Eth1/24 path
| Service | Observed degradationWhat an independent check actually saw. | Recorded exposureWhat the recorded dependencies connect to the path. | Modeled scenarioWhat would follow if the path left service. |
|---|---|---|---|
| SVC-01Records GatewayCritical | Degraded 10:09–10:31CHK-RGW-01 | RecordedSRV-01 → SW-01 → Eth1/24 path | ModeledContinues on Eth1/23 · shares TRUNK-07, SW-02 |
| SVC-04Internal directoryCritical | No degradation observedCHK-DIR-01 | RecordedSRV-02 → SW-01 → Eth1/24 path | ModeledContinues on Eth1/23 · shares TRUNK-07, SW-02 |
| SVC-02Shift rosterHigh | No degradation observedCHK-ROS-01 | RecordedSRV-01 → SW-01 → Eth1/24 path | ModeledContinues on Eth1/23 · shares TRUNK-07, SW-02 |
| SVC-03Field reports intakeStandard | Not observed · no service check | RecordedSRV-01 → SW-01 → Eth1/24 path | ModeledContinues on Eth1/23 · shares TRUNK-07, SW-02 |
SCN-NET-01 · Eth1/24 path out of serviceTraffic would rely on the secondary uplink Eth1/23. It shares TRUNK-07 and SW-02 with the primary, so continuity holds only while both remain healthy. Modeled — not observed.
Observed
Only Records Gateway was measured degraded. Where a service has no independent check, it reads “not observed”.
Recorded exposure
Being on the Eth1/24 path is not being affected. Exposure says what a service relies on, not what happened to it.
Modeled
What would carry each service if the path were taken out of service — a model, labelled as one.
Shared upstream failure domains
Redundant on paper.
Shared in practice.
A failure domain is a point every “independent” path passes through. VIPER finds them in the recorded graph and states each with its basis, what it exposes and the question it raises — for the owner to answer, not for VIPER to act on.
SW-01
Access switch · R12 U40
- Shared by
- SRV-01 and SRV-02 — all four services in the graph — and both uplinks.
- Basis
- Device inventory · surveyed 13 Oct
- Exposes
- Every service on R12’s two hosts, on either uplink.
For review Is a second access path for the critical services in scope?
TRUNK-07
MPO-8 trunk · Row A → Row C
- Shared by
- Primary uplink on channel 04, secondary on channel 03.
- Basis
- DCIM rev 14 · route documented, not surveyed
- Exposes
- Both uplinks at once if the trunk itself were cut or disturbed.
For review Should the trunk route be surveyed before it is relied on?
SW-02
Aggregation switch · R03
- Shared by
- Both uplinks since record rev 15–16 (Eth1/08 and Eth1/07).
- Basis
- Field survey rev 15 · accepted as rev 16 at 10:52
- Exposes
- New single point of failure for SVC-01 and SVC-04, reported by watch WCH-03.
For review Is the change to a shared far end intended?
UPS-01
UPS · Room 02
- Shared by
- SRV-01 supply A and supply B, after separate PDUs and breakers.
- Basis
- Recorded chain · device-reported state 11:03
- Exposes
- SVC-01, SVC-02 and SVC-03 in the modeled outage SCN-PWR-01.
For review Is a second UPS or an alternative source recorded anywhere?
Recorded versus missing
What is mapped.
What is not.
Switch between the two uplinks: the primary stops at an unresolved segment into PP-02; the secondary reaches SW-02 through a patch lead with no cable record. Neither gap is drawn in, and a drawn path is not proof that the cabling is sound.
Recorded path · Primary uplink
SW-01 Eth1/24 to SW-02 Eth1/08 through PP-01, TRUNK-07 channel 04 and PP-02.
Row A · Rack R12
Under-floor tray
Row C · Rack R03
SurveyedDocumented onlyGap · no recordHighlighting marks where evidence points — it is not a finding.
TraceRecorded to TRUNK-07 ch04. The segment into PP-02 is unresolved: LLDP names the far end, no record maps the route to it. Errors are observed at Eth1/24 only — no component on this path is established as the cause.
| Connection | Status | Source |
|---|---|---|
| SW-01 Eth1/24 → CBL-042 → PP-01 P24 | Recorded · surveyed | DCIM rev 14 · field survey 13 Oct |
| PP-01 P24 → TRUNK-07 ch04 | Documented only | DCIM rev 14 · 2 Sep |
| TRUNK-07 ch04 → PP-02 rear position | Unresolved mapping | No record · far end named by LLDP only |
| PP-02 P08 front → CBL-043 → SW-02 Eth1/08 | Recorded · surveyed | DCIM rev 14 · LLDP 10:38 |
| TRUNK-07 ch03 → PP-02 P07 | Documented only | DCIM rev 14 |
| PP-02 P07 → SW-02 Eth1/07 | No cable record | Unlabelled patch lead · REC-031 rev 16 |
| SRV-01 PSU-A / PSU-B → UPS-01 | Recorded | Power records · surveyed cords 13 Oct |
| PDU-A A14 / PDU-B B14 load | Not observed | PDUs report per-phase totals only |
Continuity scenarios
A model, with its
assumptions in view.
Each scenario states its premise, what continuity would rely on, what it assumes and what is not known. It informs the decision owner; it does not predict an outage, and it does not act.
Continuity scenarios · NYC-01
SCN-NET-01Modeled
Eth1/24 path out of service
Premise The primary uplink is taken out of service for verification or replacement.
Traffic would rely on the secondary uplink Eth1/23. It shares TRUNK-07 and SW-02 with the primary, so continuity holds only while both remain healthy. Modeled — not observed.
Would rely on
- Eth1/23 · TX-23 · CBL-041
- TRUNK-07 · ch03
- SW-02 · Eth1/07
Assumes
- Eth1/23 stays as recorded: no input errors 10:05–10:35 (OBS-0149)
- Record rev 16 is correct: the secondary terminates on SW-02
- Capacity headroom on Eth1/23 is not assessed by this scenario
Not known
- SW-02 counters on either uplink
- The physical route into PP-02
- TX-24 optics for the incident window
SCN-PWR-01Modeled
UPS-01 unavailable
Premise UPS-01 becomes unavailable while FEED-1 remains present.
Both supply paths of SRV-01 converge on UPS-01. If UPS-01 were unavailable, SRV-01 would lose both inputs and SVC-01, SVC-02 and SVC-03 would be exposed. SW-01 draws from the same PDUs. Modeled — not observed.
Would rely on
- No alternative recorded for SRV-01
- PSU-A and PSU-B both converge on UPS-01
Assumes
- The recorded chain is complete: cords, outlets, PDUs, breakers, UPS
- SW-01 draws from the same PDUs (A01 / B01), as recorded
- The vendor runtime estimate is not used to predict duration
Not known
- Per-outlet load on A14 and B14
- Any unrecorded bypass or transfer switch
Human review Scenarios inform the decision owner, ops-lead · Operations lead. The decision in force is DEC-12 — “Keep Eth1/24 in service; move traffic to Eth1/23 only if errors rise again.” — approved by netops-lead · Network operations lead. VIPER does not move traffic, change power or alter records.